Genset TP250T 227 KVA

Genset Perkins TP250T 227 KVA

STANDARDS:
Genset: GB/T2820—2009,ISO8528
Alternator: STAMFORD, UCDI274J
Diesel Engine: PERKINS , 1506A-E88TAG2
Standby Power: Continues running at variable load for duration of an emergency. No overload is permitted on these ratings.
Prime Power: Continues running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period.

Jika Perusahaan kamu membutuhkan Genset 227 KVA ?, Kita menjual Genset TP250T untuk kebutuhan Genset kapasitas 227 KVA. Berikut ini adalah spesifikasinya :

Model Engine Standby Rated
KVA KW KVA KW
TP250T 1206A-E70TTAG2 250 200 227 184

TECHNICAL SPECIFICATIONS
DIESEL GENERATING SET 400/230V-50Hz-3Phase
WEIGHT AND DIMENSIONS
STANDARDS:
Genset: GB/T2820—2009,ISO8528
Alternator: STAMFORD, UCDI274J
Diesel Engine: PERKINS , 1506A-E88TAG2
Standby Power: Continues running at variable load for duration of an
emergency. No overload is permitted on these ratings.
Prime Power: Continues running at variable load for unlimited periods
with 10% overload available for 1 hour in any 12 hour period.
CONFIGURATION:
Standard: Engine, alternator, cooling system, Base frame (excluding fuel
tank), shock absorber, air inlet system, control box (including mains floating
charge), plastic fan blades (when the engine and water tank do not bring).
Optional: Base frame (including fuel tank), water jacket heater, fuel water
separator, fuel heater, fuel level sensor (only supporting underframe tank),
switch box (with switch), power switch, the water level sensor, motor anti
condensation heater, automatic fueling system (only supporting base frame
including fuel tank), battery frame.
Accessories: Silencer, bellow, exhaust silencing system accessories (with the
matching engine), regular battery, starting cord assembly, data of gen-set,
random tool (with the matching engine.
Model
TP250T
Power(ESP)
kVA/kw
250/200
Power(PRP)
kVA/kw
227/184
Rated Voltage
V
400
Rated Current
A
361
Rated rotation speed
r/min
1500
Power Factor
0.8
Fuel Consumption
Litre/hour
48.6
Fuel Tank Capacity
Litre
Open Type :380 / Silent Type:460
Noise level
dB(A)@7m
Silent Type: 76±2
GEN-Set
Dimension ( L*W*H )
Weight
Open Type
3000mm*1150mm*1800mm
1992 Kg
Silent Type
3686mm*1406mm*1900mm
3042 Kg

 

Brand

Perkins

Scroll to Top